Connection Diagrams of SSR
SSR or Solid State Relay or Electronic Relay
Connection Diagram of AC Control SSR
Connection Diagram of SSR AC 230 Control / 230V AC N.O.
This is a Thyristor Based Normally Open 230V Switch that
can be turned on / off at a fast rate. This switches at Zero Crossover
.Built In Snubber reduces EMI and protects the SSR. USE SAME PHASE FOR
I/P & O/P.
- No moving parts hence no wear and tear.
- Dissipates Heat when in On Condition.
- Use adequate Heat Sink or SSR will fail. ( 10g / Amp)
- Dissipation is 1.5 Watts per Amp thru Load.
- Input to Output is optically isolated 2kV.
- This one is AC 230V Control AC 230V N.O. Output.
- Off state snubber Leakage is around 5 mA.

Notes -
The Termination's of High Current Lines going to Load
must be very tight and crimped. Loose contacts will Spark and cause
Fire.
Fuse Rating of HRC Fuse - High Rupture Capacity (HRC)
Fuse is Safe and Reliable. 5kW Heater at 230V is 5,000 / 230 in Amps of
Fuse Rating.
Connection Diagram of SSR DC 3-30 Control / 230V AC
N.O.
Use 12V DC for Best Results. This one is DC 3-30 Control
AC 230V N.O. Output. Rest same as above.

Connection Diagram of DC PCB SSR
Diagram of SSR 5000 DC 3-30 Control / 230V AC
N.O
3A.
This is a Thyristor Based Normally Open 230V Switch that
can be turned on / off at a fast rate. This switches at Zero Crossover
. Use 5V DC for Best Results.
- No moving parts hence no wear and tear.
- Dissipates Heat when in On Condition 5 Watts @ 3
Amps.
- Mount with adequate Air Ventilation for 3 Amps.
- Dissipation is 1.4 Watts per Amp thru Load.
- Input to Output is optically isolated 1kV.
- This one is DC 3-30 Control AC 230V N.O. Output.
- Off state snubber Leakage is around 1 mA.
Notes -
The Termination's of High Current Lines going to Load
must be very tight and crimped. Loose contacts will Spark and cause
Fire.
Fast Blow Fuse is to be used. Use a 2 Amps Fuse with
Holder in the Hot Line
Read More - Solid
State Relays SSR.
|