Electrical

You are currently browsing the archive for the Electrical category.

Liquids

20 C OHM -M
min max
Benzene 1011 1012
Transformer oil 1010 1013
Gasoline 1010 1013
Castor oil 108 1010
Acetone 104 105
Ethanol 104 105
Distilled water 103 104


Glass At High Temperature

200 C OHM -M
Sodium Pyrex 2 * 106
Potassium Pyrex 8 * 109
Lead glass 2 * 1011

Effect Of Contamination On Surface Resistivity

70% RH CONTAMINATED CLEAN
Window glass 2 * 108 1012
Fused quartz 2 * 108 1013


Relation Of Resistivity With RH % And Temp

MATERIAL 70% RH 20 deg C 0% RH 100 deg C 0% RH 20 deg C
Marble 106 - 108 1010 - 1012 1012 - 1014
Wood 106 - 107 1010 - 1012 1011 - 1013
Vulcanized fibers fibers 106 - 109 108 - 109 1011 - 1012
MATERIALS SOLIDS OHM -M


Solids

MATERIALS OHM -M
Polyethylene 1017
Poly propylene 1017
PVC 1018
Polyurethane 1015
Asbestos fiber + phenol 108
Mica + phenol 1012
Glass-fiber + polyester 1012
Glass-fiber + epoxy 1014

Standards

CBEMA - Computer Business Equipment Manufacturer’s Association
adopted curve IEEE Standard 446 (orange book) curve.

Recommended Practice for Emergency and Standby power systems for Industrial and Commercial Application.”

  • Wave form Sine wave THD (total harmonic distortion) maximum 5%.
  • 3 Phase system phase imbalance of voltage 3% - 6%.
  • Frequency stability 60 (50 Hz in India) +/- 0.5Hz.
  • Output Voltage +6% Max. -13% Min. from Nominal Value.
  • Voltage can fall to 0V but should recover in 0.5 Cycles.
  • On turn on Voltage should reach steady state within two seconds.
  • Upto 200% over Nominal Voltage should be tolerated for 100uS. ( Transients, spikes and Inductive Kickbacks come in this)
  • Upto 30% over Nominal Voltage should be tolerated for 0.5S.

ANSI - American National Standards Institute

“Standard Voltage Ratings for Electrical power systems & Equipment”

  • Steady State Variations +/- 5% of Nominal Voltage. T
  • Three Phase Voltage Imbalance 5% Max..
  • Standard Frequency 60Hz.

Glossary

  • Frequency 60Hz Hz is Hertz.
  • One Cycle = 20mS (milliseconds) one full sine wave.
  • In India Standard Frequency is 50Hz.
  • Max - Maximum
  • Min - Minimum
  • uS - micro seconds, S - seconds.

Cause of Transients

  1. Switching Loads Simultaneously (inductive loads).
  2. Power factor correction capacitors and devices.
  3. Lightning strikes (enhanced by earth faults).
  4. Line Inductance (inductive kickback, resonance).
  5. DC and AC Drives for Motors.
  6. Rectifiers with large filters and stray inductance.

Extra Reading

UPS Inverter

« Older entries

 

Pages

  • Electronic Projects

  • Reference

  • AdWords

    Recent Comments

      Edison's Gramophone

      Edison Gramophone